270kVA-270kV Series Resonance Test Device

انکوائری بھیجنے
270kVA-270kV Series Resonance Test Device
تفصیلات
MEXB-W270kVA/270kV Variable Frequency Series Resonance Test System, suitable for withstanding voltage tests on 10-110kV electrical equipment. Its volume and weight are only 1/10 to 1/30 of conventional systems. With a sine wave distortion rate < 1.0%, multiple protections, and three operating modes, it ensures safe and efficient adaptation to power testing scenarios.
مصنوعات کی درجہ بندی
AC گونجنے والا ٹیسٹ سسٹم
Share to
تصریح

270kVA-270kV Series Resonance Test Device

 

 

The main purpose of the MEXB-270kVA-270kV Variable Frequency Series Resonance Test System is to test the AC withstand voltage of 10/35/110kV cables, as well as 110kV transformers, busbars, switches, and other major electrical equipment. Because the reactors are built as several distinct units, they can be tested for low-voltage AC withstand voltage requirements, including those for 10kV cables, as well as high-voltage, low-current equipment. Because of its broad range of applications, it is a perfect withstand voltage device for power installation, maintenance, and testing engineering units as well as high-voltage testing departments at the provincial, municipal, and county levels.

The MEXB-270kVA-270kV Variable Frequency Series Resonance Test System primarily consists of a variable frequency control power supply, excitation transformer, reactors, and capacitive voltage divider.

 

1. Variable Frequency Power Supply (One Unit)

15kW;

Single-phase 380V±5% 50Hz

Adjustable 0–400V

30–300Hz

0.1Hz steps

<=0.02%

0–37.5A

2. High-Voltage Reactors (six units total)

45kV

1A

124.5

15 min

<45°C

30~300Hz

3. Excitation Transformer (one unit)

15kVA

400V

1kV/3kV/5kV/20kV

15A/5A/3A/0.75A

4. Capacitive Divider (One Set)

Self-Capacitance

1000pF

300kV

30–300Hz

1.5%

300kV/1000pF

5. Test Lead Set and Accessories (One Set)

1) Internal Connection Cables (One Set)

2) Reactor Insulation Bases (Six Pieces)

3) Equalizing Rings (One Pair)

4) Divider and Reactor Supports (Two Sets)

 

 

1. The device has protective features for overvoltage, overcurrent, zero-position start, and system detuning (flashover). The thresholds for overvoltage and overcurrent protection can be changed to suit the needs of the user. The flashover protection turns on during specimen flashover and logs the flashover voltage measurement for test analysis.

2. Because each unit is lightweight, on-site operation is made easier.

3. To improve testing efficiency, the gadget has three operating modes that users can choose according to site conditions.
Three operating modes are available: Auto-Tuning Manual Voltage Increase Mode, Fully Automatic Mode, and Manual Mode.

4. Remote data storage and printing is possible. Numerical identifiers are assigned to stored data to facilitate user recognition and retrieval.

5. The beginning frequency can be flexibly adjusted within the designated range during automatic frequency sweeping. It is possible to choose an upward or downward sweep direction. Users can easily identify resonant point detection by viewing the scan curve on the huge LCD screen.

6. Makes use of DSP platform technology, which improves the user-friendly human-machine interface and for the flexible addition or removal of features and improvements based on user needs.

 

1. AC Withstand Voltage Test for 10/35/110kV Cross-linked Polyethylene Cables

2. AC Withstand Voltage Test for 110kV Transformers, Line Insulators, Switches, GIS, and Other Primary Electrical Equipment

 

 

 

1)What advantages does the MEXB-W270kVA/270kV variable frequency series resonant test device gain by adopting DSP platform technology?

Answer: The adoption of DSP platform technology enables this device to conveniently add or remove functional modules based on actual user requirements. It also facilitates post-production upgrades and iterations of product functionality, adapting to a wider range of test scenarios. Additionally, it enhances the user interface with greater intuitiveness and clearer operational logic, reducing the learning and usage difficulty for operators while improving the overall convenience of test operations.

2)During testing, if the MEXB-W270kVA/270kV variable frequency series resonant test device fails to start its fan, what are the possible causes?

Answer: Two potential causes exist: First, if the device undergoes an emergency stop, fault protection, or detuning protection, and the operator fails to press the "Fault Reset" button, the fan cannot start normally. Second, excessive internal temperature may trigger thermal protection in the power components, thereby interrupting the fan's operating circuit.

3)The touchscreen display of the MEXB-W270kVA/270kV variable frequency series resonance test set features a "Parameter Calculation" function. What operations does this function enable?

Answer: The "Parameter Calculation" function supports inputting any two known values from the three physical quantities: inductance, capacitance, and frequency. The system automatically calculates the third unknown quantity. Operators can use this function to quickly obtain key parameters required for testing, providing data references for formulating and adjusting test plans, thereby enhancing test preparation efficiency.

 

ڈاؤن لوڈ، اتارنا ٹیگ: 270kva-270kv series resonance test device, China 270kva-270kv series resonance test device manufacturers, factory

انکوائری بھیجنے